  • OEM vfd 5 Hp 460v 220v Single Phase manufacturer

    The control core of the ZYV6 AC drive is based on a 32-bit RISC microcontroller. Its operation speed can complete efficient and complex motor control algorithms. It perfectly combines vector control and VF control technology to improve load torque response in a timely manner to meet customers' wide range of variable torque loads need.

    • Power range 0.75kW~200kW
    • Voltage level AC 1PH/3PH 220V
    • AC 3PH 380V

    ZYV6-7R5G-011P-4omi

    ●Has advanced open-loop vector control performance and good voltage and current control technology;

    ●Starting torque: 0.5Hz/150% torque;

    ●Wide voltage range design, the wide voltage range reaches AC 3PH: 360V~450V;

    ●Inverters below 18.5kW (inclusive) have built-in braking units;

    ●Has the function of not shutting down in case of instantaneous power failure;

    ●Independent air duct design supports wall-mounted and floor-standing installation methods, providing customers with a more reliable and economical installation and use method.

    Project

    Technical Parameters

    Enter

    Rated voltage

    3PH AC 380V

    Frequency

    50Hz/60Hz

    Voltage allowable variation range

    3PH AC 360V~450V

    Output

    Voltage

    0~440V

    Frequency

    Low frequency mode:0~300Hz  High frequency mode:0~3000Hz

    Overload capacity

    G type machine: 110% long term; 150% 1 minute; 180% 1 second

    P type machine: 105% long term; 120% 1 minute; 150% 1 second

    Control characteristics

    Control method

    0: Ordinary V/F control; 1: Advanced V/F control: 2: Open-loop current vector control; 3: Separate V/F control

    Modulation

    Space voltage vector PWM modulation

    Starting torque

    150% rated torque at 0.5Hz (vector type V/F control)

    Frequency accuracy

    Digital setting: maximum frequency´+0.01%; analog setting: maximum frequency´±0.2%

    Frequency resolution

    Digital setting: 0.01Hz;Analog setting: Maximum frequency´0.05%

    Torque boost

    Automatic torque boost, manual torque boost 0.1% to 30.0%

    V/F curve

    0: Linear curve 1: Decreasing torque curve 1 (1.3 power)

    2: Torque reduction curve 2 (1.5 power) 3: Torque reduction curve 3 (1.7 power)

    4: Square curve 5: User-set V/F curve

    Acceleration and deceleration curve

    Three methods: linear acceleration and deceleration, S-curve acceleration and deceleration, and shortest acceleration and deceleration;

    Four acceleration and deceleration times, time unit (minute/second) optional

    DC braking

    Stop DC braking starting frequency: 0.00Hz~maximum output frequency;

    Braking time: 0.0~50.0s; Braking current: 0.0%~150.0% rated current

    Automatic voltage regulation (AVR)

    When the grid voltage changes, it can automatically keep the output voltage constant

    Automatic current limit

    Automatically limit the current during operation to prevent frequent overcurrent fault tripping

    Automatic carrier adjustment

    Automatically adjust carrier frequency according to load characteristics and temperature characteristics

    Run function

    Run command channel

    The operation panel, control terminal and serial port can be switched in a variety of ways.

    Frequency given channel

    Digital given, analog voltage given, analog current given, pulse given, serial port given, terminal given, multi-speed given, can be switched in a variety of ways

    Auxiliary frequency given

    Realize flexible auxiliary frequency fine-tuning and frequency combination calculations

    Pulse output terminal

    0~50kHz pulse square wave signal output, which can realize the output of physical quantities such as set frequency and output frequency.

    Analog output terminal

    2 analog signal outputs, each optional 0/4~20mA or 0/2~10V, can realize the output of physical quantities such as set frequency and output frequency.

    Operation panel

    LED display

    Can display 61 parameters such as set frequency, output frequency, output voltage, output current, etc.

    Button function selection

    Define the scope of some keys to prevent misoperation

    Protective function

    Phase loss protection (optional), overcurrent protection, overvoltage protection, undervoltage protection, overheating protection, overload protection, load loss protection, etc.

    Environment

    Place of use

    Indoor, no direct sunlight, no corrosion, no flammable gas, no oil mist, dust, etc.

    Ambient temperature

    -10℃~+40℃(The ambient temperature is between 40℃ and 50℃, please derate it for use.)

    Ambient humidity

    5%~95%RH,No water droplets condensation

    Altitude

    Derate for use above 1000 meters, and derate by 10% for every 1000 meters.

    Structure

    Protection level

    IP20

    Cooling method

    Air-cooled, with fan control

    Installation method

    Wall-mounted, cabinet type